Wednesday, 31 August 2016
Size of Room
Habitable Room
Water Closet/Bathroom
1) The size of independent water-closet shall be 0.90 m2 with minimum width of 0.9 m;
2) The size of independent bathroom shall be 1.20 m2 with a minimum width of 1.0 m; and
3) The size of combined bathroom and watercloset shall be 1.80 m2 with minimum width of 1.0 m.
Kitchen
Balcony
Habitable Room
Every dwelling unit to be provided should have at least
two habitable rooms. Even if one room house is
provided initially it should be capable of adding a new
second room in future. However, in case single room
tenements are required to be provided where future
additions are not possible, the carpet area of
multipurpose single room should be at least 12.5 m2.
Such one room dwelling units with 12.5 m2 carpet area
of habitable space is permitted only in case of on site
rehabilitation of slum dwellers. In a house of two
rooms, first room shall not be less than 9.0 m2 with
minimum width of 2.5 m and second room shall not
be less than 6.5 m2 with a minimum width of 2.1 m
provided the total area of both the rooms is not less
than 15.5 m2
. In incremental housing the bigger room
shall always be the first room.
To facilitate incremental housing in case of
flatted development or otherwise, habitable space at
mezzanine level may be permitted. The minimum size
of such a mezzanine floor should not be lesser than
6.5 m2 and such a floor should occupy not more than
50 percent of the room area of which it is a part. Such
a mezzanine floor should have appropriate openings
to facilitate light and ventilation as per
Minimum clear height below and above the mezzanine floor
should be 2.4 m and 2.1 m respectively.
As far as possible mezzanine floor should have direct
ventilation from the external face of the building.
Where this is not possible ventilation through main
room may be allowed provided total area of openings
in the main room is provided taking into consideration
area of mezzanine floor.
Such mezzanine floor may be accessible through the
main room by a ladder, whose minimum angle with
vertical plane should be 22½°. Height of the riser
should be less than 250 mm.
Water Closet/Bathroom
1) The size of independent water-closet shall be 0.90 m2 with minimum width of 0.9 m;
2) The size of independent bathroom shall be 1.20 m2 with a minimum width of 1.0 m; and
3) The size of combined bathroom and watercloset shall be 1.80 m2 with minimum width of 1.0 m.
Kitchen
The size of a cooking alcove serving as cooking space
shall not be less than 2.4 m2
with a minimum width of
1.2 m. The size of individual kitchen provided in a
two-roomed house shall not be less than 3.3 m2
with a
minimum width of 1.5 m.
Balcony
The minimum width of individual balcony, where
provided, shall be 0.9 m and shall not be more than
1.2 m and it shall not project beyond the plot line and
on roads or pathway.
Staircase/Exit Requirements
Minimum width — The minimum width of staircase shall be as follows:
a) Residential buildings (dwellings) 1.0 m
NOTE — For row housing with 2 storeys, the minimum width shall be 0.75 m.
b) Residential hotel buildings 1.5 m
c) Assembly buildings like 2.0 m auditorium, theatres and cinemas
d) Educational building 1.5 m
e) Institutional buildings 2.0 m
f) All other buildings 1.5 m
Minimum tread
Maximum riser
The minimum clear width, minimum tread
width and maximum riser of staircases for buildings
shall be as given as follows:
Minimum width — The minimum width of staircase shall be as follows:
a) Residential buildings (dwellings) 1.0 m
NOTE — For row housing with 2 storeys, the minimum width shall be 0.75 m.
b) Residential hotel buildings 1.5 m
c) Assembly buildings like 2.0 m auditorium, theatres and cinemas
d) Educational building 1.5 m
e) Institutional buildings 2.0 m
f) All other buildings 1.5 m
Minimum tread
The minimum width of tread without nosing shall be
250 mm for residential buildings. The minimum width
of tread for other buildings shall be 300 mm.
Maximum riser
The maximum height of riser shall be 190 mm for
residential buildings and 150 mm for other buildings
and these shall be limited to 12 per flight.
**The minimum head-room in a passage under
the landing of a staircase shall be 2.2 m. The minimum
clear head-room in any staircase shall be 2.2 m.
Bathrooms and Water-Closets
Height
The height of a bathroom or water-closet measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be less than 2.1 m.
Size
The area of a bathroom shall not be less than 1.8 m2 with a minimum width of 1.2 m. The floor area of water-closet shall be 1.1 m2 with a minimum width of 0.9 m. If bath and water-closet are combined, its floor area shall not be less than 2.8 m2 with a minimum width of 1.2 m.
Other Requirements Every bathroom or water-closet shall:
a) be so situated that at least one of its walls shall open to external air;
b) not be directly over or under any room other than another water-closet, washing place, bath or terrace, unless it has a water-tight floor;
c) have the platform or seat made of water-tight non-absorbent material;
d) be enclosed by walls or partitions and the surface of every such wall or partition shall be finished with a smooth impervious material to a height of not less than 1 m above the floor of such a room;
e) be provided with an impervious floor covering, sloping towards the drain with a suitable grade and not towards VERANDAH or any other room; and
f) have a window or ventilator, opening to a shaft or open space, of area not less than 0.3 m2 with side not less than 0.3 m.
**No room containing water-closets shall be used for any purpose except as a lavatory and no such room shall open directly into any kitchen or cooking space by a door, window or other opening. Every room containing water-closet shall have a door completely closing the entrance to it.
Height
The height of a bathroom or water-closet measured from the surface of the floor to the lowest point in the ceiling (bottom of slab) shall not be less than 2.1 m.
Size
The area of a bathroom shall not be less than 1.8 m2 with a minimum width of 1.2 m. The floor area of water-closet shall be 1.1 m2 with a minimum width of 0.9 m. If bath and water-closet are combined, its floor area shall not be less than 2.8 m2 with a minimum width of 1.2 m.
Other Requirements Every bathroom or water-closet shall:
a) be so situated that at least one of its walls shall open to external air;
b) not be directly over or under any room other than another water-closet, washing place, bath or terrace, unless it has a water-tight floor;
c) have the platform or seat made of water-tight non-absorbent material;
d) be enclosed by walls or partitions and the surface of every such wall or partition shall be finished with a smooth impervious material to a height of not less than 1 m above the floor of such a room;
e) be provided with an impervious floor covering, sloping towards the drain with a suitable grade and not towards VERANDAH or any other room; and
f) have a window or ventilator, opening to a shaft or open space, of area not less than 0.3 m2 with side not less than 0.3 m.
**No room containing water-closets shall be used for any purpose except as a lavatory and no such room shall open directly into any kitchen or cooking space by a door, window or other opening. Every room containing water-closet shall have a door completely closing the entrance to it.
Kitchen
Height
Size
Other Requirements
Every room to be used as kitchen shall have:
c) a flue, if found necessary.
Height
The height of a kitchen measured from the surface of the floor to the lowest point in the ceiling (bottom slab) shall not be less than 2.75 m, except for the portion to accommodate floor trap of the upper floor.
Size
The area of a kitchen where separate dining area is provided, shall be not less than 5.0 m2 with a minimum width of 1.8 m. Where there is a separate store, the area of the kitchen may be reduced to 4.5 m2. A kitchen, which is intended for use as a dining area also, shall have a floor area of not less than 7.5 m2 with a minimum width of 2.1 m.
Other Requirements
Every room to be used as kitchen shall have:
a) unless separately provided in a pantry, means for the washing of kitchen utensils which shall lead directly or through a sink to a grated and trapped connection to the waste pipe;
b) an impermeable floor;c) a flue, if found necessary.
Habitable Rooms
Height
b) Industrial Buildings Ceiling height 3.6 m, except when air-conditioned, 3 m
(For Factory seperate rules therein shall govern such heights, where applicable, with their respective country codes).
Size
Height
The height of all rooms for human habitation shall not be less than 2.75 m measured from the surface of the floor to the lowest point of the ceiling (bottom of slab). In the case of pitched roof, the average height of rooms shall not be less than 2.75 m. The minimum clear head room under a beam, folded plates or eaves shall be 2.4 m. In the case of air-conditioned rooms, a height of not less than 2.4 m measured from the surface of the floor to the lowest point of air-conditioning duct or the false ceiling shall be provided. The above requirements apply to residential, business and mercantile buildings. For educational and industrial buildings, the following minimum requirements apply:
a) Educational Buildings Ceiling height 3.6 m for all regions; in cold regions, 3 mb) Industrial Buildings Ceiling height 3.6 m, except when air-conditioned, 3 m
(For Factory seperate rules therein shall govern such heights, where applicable, with their respective country codes).
Size
The area of habitable room shall not be less than 9.5 m2, where there is only one room with a minimum width of 2.4 m. Where there are two rooms, one of these shall not be less than 9.5 m2 and the other not less than 7.5 m2, with a minimum width of 2.1 m.
Tuesday, 23 August 2016
Socio-cultural facilities
Land Area Required, Min
1) Community room (1 for every 5 000 population) Area 750 m2
2) Community hall, mangal karyayala/kalyana mandapam/barat ghar/library
(1 for every 15 000 population) Area 2 000 m2
3) Recreational club (1 for every 100 000 population) Area 10 000 m2
4) Music, dance and drama centre (1 for every 100 000 population) Area 1 000 m2
5) Meditation and spiritual centre (1 for every 100 000 population) Area 5 000 m2
6) Socio-cultural centre (1 for every 1 000 000 population) Area 15 ha
Land Area Required, Min
1) Community room (1 for every 5 000 population) Area 750 m2
2) Community hall, mangal karyayala/kalyana mandapam/barat ghar/library
(1 for every 15 000 population) Area 2 000 m2
3) Recreational club (1 for every 100 000 population) Area 10 000 m2
4) Music, dance and drama centre (1 for every 100 000 population) Area 1 000 m2
5) Meditation and spiritual centre (1 for every 100 000 population) Area 5 000 m2
6) Socio-cultural centre (1 for every 1 000 000 population) Area 15 ha
DEVELOPMENT CONTROL RULES AND GENERAL BUILDING REQUIREMENTS
a) Pre-Primary to Secondary Education
1) Pre-primary, nursery school (1 for every 2 500 population)
i) Area per school 0.08 ha
ii) Location of pre-primary/nursery school Near a park
2) Primary school (class 1 to 5) (1 for every 5 000 population)
i) Strength of school —------------------------------------------------------------------------------500 students
ii) Area per school 0.40 ha
a) School building area 0.20 ha
b) Play field area (with a minimum of 18 m × 36 m to be ensured for effective play) 0.20 ha
3) Senior secondary school (class 6 to 12) (1 for every 7 500 population)
i) Strength of the school —-------------------------------------------------------------------------1000students
ii) Area per school 1.80 ha
a) School building area 0.60 ha
b) Play field area (with a minimum of 68 m × 126 m to be ensured for effective play) 1.00 ha
c) Parking area 0.20 ha
4) Integrated school without hostel facility (class 1 to 12) (1 for every 90 000 to 100 000
population)
i) Strength of the school—-------------------------------------------------------------------------1500students
ii) Area per school 3.50 ha
a) School building area 0.70 ha
b) Play field area 2.50 ha
c) Parking 0.30 ha
5) Integrated school with hostel facilities (class 1 to 12) (1 for every 90 000 to 100 000
population)
i) Strength of school —----------------------------------------------------------------------------1500students
ii) Area per school 3.90 ha
a) School building area 0.70 ha
b) Play field area 2.50 ha
c) Residential (including hostel area) 0.40 ha
d) Parking area 0.30 ha
6) School for physically challenged (class 1 to 12) (1 for every 45 000 population)
i) Strength of school —----------------------------------------------------------------------------400 students
ii) Area per school 0.70 ha
a) School building area 0.20 ha
b) Play field area 0.30 ha
c) Parking area 0.20 ha
a) Pre-Primary to Secondary Education
1) Pre-primary, nursery school (1 for every 2 500 population)
i) Area per school 0.08 ha
ii) Location of pre-primary/nursery school Near a park
2) Primary school (class 1 to 5) (1 for every 5 000 population)
i) Strength of school —------------------------------------------------------------------------------500 students
ii) Area per school 0.40 ha
a) School building area 0.20 ha
b) Play field area (with a minimum of 18 m × 36 m to be ensured for effective play) 0.20 ha
3) Senior secondary school (class 6 to 12) (1 for every 7 500 population)
i) Strength of the school —-------------------------------------------------------------------------1000students
ii) Area per school 1.80 ha
a) School building area 0.60 ha
b) Play field area (with a minimum of 68 m × 126 m to be ensured for effective play) 1.00 ha
c) Parking area 0.20 ha
4) Integrated school without hostel facility (class 1 to 12) (1 for every 90 000 to 100 000
population)
i) Strength of the school—-------------------------------------------------------------------------1500students
ii) Area per school 3.50 ha
a) School building area 0.70 ha
b) Play field area 2.50 ha
c) Parking 0.30 ha
5) Integrated school with hostel facilities (class 1 to 12) (1 for every 90 000 to 100 000
population)
i) Strength of school —----------------------------------------------------------------------------1500students
ii) Area per school 3.90 ha
a) School building area 0.70 ha
b) Play field area 2.50 ha
c) Residential (including hostel area) 0.40 ha
d) Parking area 0.30 ha
6) School for physically challenged (class 1 to 12) (1 for every 45 000 population)
i) Strength of school —----------------------------------------------------------------------------400 students
ii) Area per school 0.70 ha
a) School building area 0.20 ha
b) Play field area 0.30 ha
c) Parking area 0.20 ha
Thursday, 18 August 2016
Construction Joint
Although there is no technical limitation to the area that may be concreted, the usual pour area is up to 1 000 m2/day. Where the limits of the pour do not coincide with permanent slab edges, construction joints are used to define the extent of the pour.
The locations and details of the construction joints may have an effect on the cracking. The layout and details of the joints shall be determined by the structural designer. For example, when brittle bonded finishes are used, the relationship between the joints in the concrete and the joints in the finishes shall be considered at the outset, to reduce the risk of cracking in undesirable locations.
Where possible, the construction joints shall be located close to butt joints in the decking. Where shear connectors are used, it is preferable to create the joint to one side of the line of the shear connectors, to ensure sound concrete around the studs. If the construction joint cannot be made near a butt joint, it is suggested that no more than one-third of the decking span from a butt joint shall be left un-poured. Concreting shall not be stopped within a sheet length, because excessive deflections may occur when the loads on a continuous decking sheet are not balanced either side of the intermediate support beam.
Stop ends, usually in the form of timber or plastic inserts, are used to create the construction joints. As with all the joints and ends of the decking, they shall be checked for potential grout loss.
Type of Formwork Minimum Period
Before Striking
Formwork
a) Vertical formwork to
columns, walls, beams 16-24 h
b) Soffit formwork to slabs
(Props to be refixed
immediately after removal
of formwork) 3 days
c) Soffit formwork to beams
(Props to be refixed
immediately after removal
of formwork) 7 days
d) Props to slabs:
1) Spanning up to 4.5 m 7 days
2) Spanning over 4.5 m 14 days
e) Props to beams and arches:
1) Spanning up to 6 m 14 days
2) Spanning over 6 m 21 days
Before Striking
Formwork
a) Vertical formwork to
columns, walls, beams 16-24 h
b) Soffit formwork to slabs
(Props to be refixed
immediately after removal
of formwork) 3 days
c) Soffit formwork to beams
(Props to be refixed
immediately after removal
of formwork) 7 days
d) Props to slabs:
1) Spanning up to 4.5 m 7 days
2) Spanning over 4.5 m 14 days
e) Props to beams and arches:
1) Spanning up to 6 m 14 days
2) Spanning over 6 m 21 days
Wednesday, 17 August 2016
Building Plan and Details
The plan of the buildings and elevations and sections accompanying the notice shall be drawn to a scale of 1 : 100. The plans and details shall:
a) Include floor plans of all floors together with the covered area clearly indicating the size and spacing of all framing members and sizes of rooms and the position of staircases, ramps and lift wells;
b) Show the use or occupancy of all parts of the buildings;
c) Show exact location of essential services, for example, WC, sink, bath and the like;
d) Include at least one elevation from the front showing height of building and rooms and also the height of parapet;
e) Include at least one section through the staircase;
f) Include the structural arrangements with appropriate sections showing type/arrangement of footings, foundations, basement walls; structural load bearing walls, columns and beams, and shear walls; and arrangement/spacing of framing members, floor slabs and roof slabs with the material used for the same;
g) Show all street elevations;
h) Give dimensions of the projected portions beyond the permissible building line;
j) Include terrace plan indicating the drainage and the slope of the roof; and
k) Give indications of the north point relative to the plan.
NOTE — The requirement of 1 : 100 is permitted to be flexible for specific details needed for further
illustration; and also for drawings for these in electronic form.
Structural Sufficiency Certificate
The plans shall be accompanied by structural sufficiency certificate in the prescribed form (see Annex C) signed by the engineer/structural engineer (see Annex A) and the owner jointly to the effect that the building is safe against various loads, forces and effects including due to natural disasters, such as, earthquake, landslides, cyclones, floods, etc as per Part 6 (NBC) ‘Structural Design’ and other relevant Codes. The engineer/structural engineer shall also have the details to substantiate his design.
Storage of Cement
Cement can be safely stored in sacks for a few months if kept in dry and air-tight room. If prolonged storage of cement is unvoidable, it is better to empty the bags and stock the cement in as deep a heap as possible in a damp-proof enclosed space. Paper sacks are better than jute sacks as regards deterioration by moisture. Cement stored for more than six months should be tested for soundness before use on all important works and which period mar be three months when stored in jute bags. Concrete made with storage-deteriorated cement takes longer to harden.
Cement in bags should be stored in a dry room on a raised wooden platform 15 to 23 cm above the floor level and 30 cm away from walls. Bags to be stacked in not more than 10 layers high (max 4.5m) to prepare bursting of the bags in bottom layers. The bags should be placed close together to reduce circulation of air and all openings in the room should also be well closed. If the piles are to be more than seven or eight bags high, the bags should be placed in header and stretchers, i.e., alternatively lengthwise and crosswise.
Monday, 15 August 2016
Sunday, 14 August 2016
Bent- Up Bars
In simply supported single span slabs it is not normally necessary to bent up any bars. But in partially fixed conditions (which are the most common and occur where roof slabs are built into walls) every third bar shall be bent up. In the slabs continous over two or more spans, alternate bars may be bent up, or equivalent seperate reinforcement may be provided at the top of the supports for the negative moments. Bent-up bars are more economical. In large slabs seperate reinforcement over the siupports may be necessary.
Such bent-up bars shall extend a sufficient distance beyond the centre of the support to provide adequate bond. The points at which some of the reinforcement is bent-up for the negative bending moment at the support depend on the points of contraflexure. Stirrups are not used in slabs.
It is not necessary to check shear or bond stress on a slab except with a superimposed load of over 2000 Kg per Meter Square. Shear stress in concrete is generally small and bond stress within allowable limits.
DESIGN OF RC BEAMS
Practical Rules
1. The over-all depth of a singly reinforced rectangular beam shall be not less than 1/20 of the span unless shear and other consideration prevail. The greater depth the less in the steel required and more economical is the beam, but there is a limit to it.
For the adequate safety against deformation and cracking, international code of reinforcement concrete (1970) recommends a minimum beam depth for both rectangular and T-Beam to be equal to or greater than 1/12 of the span length. For designing the beam depth may be assumed as 1/10 to 1/12 of the span for simply supported beams and 1/12 to 1/18 for continuous beams.
2. The breath of a beam shall normally be 2/3 to 1/2 of the depth, but not less than 1/3 of the depth. A good rule fot the breath is to take 3/5th of the depth of the beam.
Where the span/breath ratio exceeds 30 (beam whose length between adequate lateral restraints exceeds 30 times the breath of its compression flange) and it is not practicable to support the compression flange laterally, the permissble compressive stress in the concrete due to bending shall be reduced by a factor (1.75-L/40B), where L is the length of the beam lateral restraints, i.e.-free span and B is the breath of the compression flange. The permissible stress in the compression reinforcement (where provided) shall also be reduced in the stress ratio.
Slenderness Limits for the Beam to Ensure Lateral Stability : A Simply supported or continuous beam shall be so proportioned that the clear distance between the lateral restraints does not exceed 60b or 250 b*b/d, whichever is less; where d is the effective depth of the beam and b the breadth of the compresssion face midway between the lateral restraints. For a cantilever, the clear distance from the free end of the cantilever to the lateral restraints shall not exceed 25b or 100 b*b/d, which ever is less. (IS :456-1978).
Beams are often used to supported slabs whcih are mostly cast with beams as a monolithic construction and designed as T-beams. (See also under "Lareral Stability of Beams" in section 10). This condition of lateral support can be deemed to be satisfied by a slab monolithic with beam near its compression flange provided the slab thickness is not less than 1/10 of the beam depth and adequate top and bottom reinforcement, suitably anchored, has been provided at the beam slab junction.
The clear distance from the corner of a beam or rib to the nearest longitudinal bar should be not less than 8 cm.
If depth of the beam exceeds 60 cm, skin reinforcement, on both faces of web, in the form of longitudinal bars (minimum 12 bar dia and spacede not more than 20 cm) should be provided. Such skin reinforcement on each face should be at least 0.05 percent of gross web area.
The top surface of centering should be givien a camber of 5 mm for every meter of span subject to a maximum of 35 mm, to allow for the initial deflection settlement.
Reinforcement
Minimum tensile reinforcement in beams shall be not less than 0.30 percent where plain bars are used and 0.20 percent where high-yield strength deformed bars are used of the gross cross-sectional area of the beam. The maximum area of tension reinforcement shall not exceed 4 percent. The area of beam being calculated as total cross-sectional area for rectangular beams and as area equal to overall depth multiplied by the width if the web in the case of T or L beam. At least one-fourth of the tension steel should be carried straight into the support so as to provide anchorage.
Spacing of Reinforcement Bars
The horizontal clear space between two parallel main reinforcement bars shall be not less than the greatest of the following:
(a) The diameter of the bar if the diameter are equal, (b) the diameter of the larger bar if the diameters are unequal, (c) 5 mm more than the nominal maximum size of the coarse aggregate used in the concrete. Greater horizontal spacing than the minimum specified shall be provided where provisios.
This does not preclude the use of larger size of aggregate beyond the congested reinforcement in the same member; the size of the coarse aggregates may be reduced around the congested reinforcement to comply with the above provisions.
Where needle or immersion vibrators are intended to be used, the horizontal distance between bars of a group may be reduced to two-thirds of the nominal maximum size of the coarse aggregate provided that sufficient space is left between groups of bars to enable the vibrator to be immersed.
The clear vertical space between two horizontal main reinforceing bars shall normally be 15 mm, the maximum size of the coarse aggregate or the maximum size of the bar, whichever is tha largest. Bars can also be placed one above the other without any space in-between. Steel space-bars may be introduced to maintain correct horizontal and vertical distance apart of the bars.
Main tensile reinforcement bars in beams shall be not less than 12 mm in dia. Use as few different dia as possible. Additional bars at the top corners have usually to be provided in beams for bending the stirrups for shear. Diameters of these bars may be 10 mm when not required to take any bending moments.
Wednesday, 10 August 2016
General Building Requirement (Homestead)
Water-Closet/Bathroom
a) The size of independent water-closet shall be 0.9 m2; with minimum width of 90 cm.
b) The size of independent bathroom shall be 1.2 m2 with minimum width of 1m, and
c) The size of combined bath and water closet shall be 1.8 m2 with minimum width of 1 m.
Source : National Building Code
Water-Closet/Bathroom
a) The size of independent water-closet shall be 0.9 m2; with minimum width of 90 cm.
b) The size of independent bathroom shall be 1.2 m2 with minimum width of 1m, and
c) The size of combined bath and water closet shall be 1.8 m2 with minimum width of 1 m.
Source : National Building Code
Tuesday, 9 August 2016
Conduit Colour Coding (For Pipes Passing Through Walls & Floors)
The conduits shall be colour coded as per the
purpose of wire carried in the same. The
colour coding may be in form of bands of
colour (4 inch thick, with centre-to-centre
distance of 12 inches) or coloured throughout
in the colour. The colour scheme shall be as
follows:
Conduit Type Colour scheme
Power conduit Black
Security conduit Blue
Fire alarm conduit Red
Low voltage conduit Brown
UPS conduit Green
Slipform
Slipform is a continuously moving form at such a speed
that the concrete when exposed has already achieved
enough strength to support the vertical pressure from
concrete still in the form as well as to withstand
nominal lateral forces. Slipform may be classified as
straight slipform, tapering slipform and slipform for
special applications. Construction of lift cores and
stairwell using slipform technique comes under special
applications because of their complex sizes, shapes and
loads to be lifted alongwith the slipform like walkway
truss, etc, which is essential for construction. This
system uses hydraulic jacks avoiding crane for lifting
of assembly during construction operation. This system
facilitates rapid construction and continual casting,
creating a monolithic structure thereby avoiding
construction joints.
Source : NBC Of India - Part 6, Section 7.
Shop Drawing
Shop Drawings, giving complete information necessary
for the fabrication of the component parts of the
structure including the location, type, size, length and
detail of all welds, shall be prepared in advance of the
actual fabrication. They shall clearly distinguish
between shop and field rivets, bolts and welds. For
additional information to be included on drawings for
designs based on the use of welding, reference shall
be made to appropriate Indian Standards. Shop
drawings shall be made in accordance with good
practice. A marking diagram allotting distinct
identification marks to each separate part of steel work
shall be prepared. The diagram shall be sufficient to
ensure convenient assembly and erection at site.
Source : NBC Of India, Part - 6
Overloading - Pile
When a pile in a group, designed for a certain safe
load is found, during or after execution, to fall just
short of the load required to be carried by it, an overload
of up to 10 percent of the pile capacity may be allowed
on each pile. The total overloading on the group should
not be more than 10 percent of the capacity of the group
nor more than 40 percent of the allowable load on a
single pile.
Source : National Building Code
Monday, 8 August 2016
Behaviour Of Single Bay Two Storeys RC Frame
Abstract
Multi-storeyed Reinforced Concrete (RC) framed structures are being constructed extensively in India of-late. The RC elements of the frame are generally designed to take up all the loads and masonry walls are often considered as non-structural filler materials. These RC framed structures suffer premature failures when subjected to lateral forces resulting due to cyclic load nature of seismic forces. This paper discusses about the behaviour of single bay two storied RC frame subjected to lateral loads. The paper also discusses on the aspects of ductility, stiffness degradation, and energy absorption and failure mechanisms of RC frame subjected to cyclic loading.Keyword : RCC Frame, Masonry Infill, Stiffness degradation
Author : R.AmuthaSelvaKumar, M.Mohana Ram.
To Download, Click The Link https://www.academia.edu/25186876/Behavior_of_Single_Bay_Two_Storeys_RC_Frame
Comparisons of the Different Bracing System with Lateral and Transverse Loading on 2D Steel Frame
Abstract
This paper is for identifying the effective bracing system for different kind of loading system like lateral loading and transverse loading of the 2D steel frame. In this paper basic types of bracing are analysed with an example models and compared.Keyword : Bracing, Chevron, X-Cross, Inverted Chevron, Diagonal, 2D Frame, Lateral and Transverse loading
Author : M.Mohana Ram
Subscribe to:
Posts (Atom)