Staircase/Exit Requirements
Minimum width — The minimum width of staircase shall be as follows:
a) Residential buildings (dwellings) 1.0 m
NOTE — For row housing with 2 storeys, the minimum width shall be 0.75 m.
b) Residential hotel buildings 1.5 m
c) Assembly buildings like 2.0 m auditorium, theatres and cinemas
d) Educational building 1.5 m
e) Institutional buildings 2.0 m
f) All other buildings 1.5 m
Minimum tread
Maximum riser
The minimum clear width, minimum tread
width and maximum riser of staircases for buildings
shall be as given as follows:
Minimum width — The minimum width of staircase shall be as follows:
a) Residential buildings (dwellings) 1.0 m
NOTE — For row housing with 2 storeys, the minimum width shall be 0.75 m.
b) Residential hotel buildings 1.5 m
c) Assembly buildings like 2.0 m auditorium, theatres and cinemas
d) Educational building 1.5 m
e) Institutional buildings 2.0 m
f) All other buildings 1.5 m
Minimum tread
The minimum width of tread without nosing shall be
250 mm for residential buildings. The minimum width
of tread for other buildings shall be 300 mm.
Maximum riser
The maximum height of riser shall be 190 mm for
residential buildings and 150 mm for other buildings
and these shall be limited to 12 per flight.
**The minimum head-room in a passage under
the landing of a staircase shall be 2.2 m. The minimum
clear head-room in any staircase shall be 2.2 m.